Drift eliminators are used to capture water droplets in the air stream that otherwise would be lost to the atmosphere. Entrapping these droplets is important for not only conserving water as a resource but also to prevent cooling tower water from contaminating the area peripheral to the cooling tower.
The cooling tower industry uses drift rate to compare drift eliminator performance, a relationship that correlates droplet capture efficiency to the water circulation rate in a tower.
R.V Cooling’s drift eliminators are specifically designed to achieve maximum drift removal efficiency in both cross flow and counter flow tower applications with various product options available to minimize pressure drop, drift loss, cost, or a combination of all three.
Characteristics | CD-S130/CD-S146 |
---|---|
Material | Rigid PVC |
Maximum Face Velocity | 4.5 m/sec |
Module Length | Can be chosen in 600-mm increments. Max suggested length – 1800-mm |
Module Depth | 130 / 146 mm |
Pitch | 20 mm |
Maximum Spacing of Support with standard thickness of sheets | 800 mm |
Directional changes for air flow | 3 |
Standard Thickness (Corrugated/Plain) | 0.3mm/0.4mm |
Average Weight | 7.6 / 8.5 kgs/m2 |
Expected Drift Loss | < 0.001% / 0.0005% of circulating water |
Maximum Continuous Temperature (deg Celsius) | 55°C |
Characteristics | CDS130 | CDS145 |
Type Of Structure | Cellular | Cellular |
Maximum Face Velocity | 4.5 m/sec | 4.5 m/sec |
Module Length | Can be chosen | Can be chosen |
Module Width | Can be chosen | Can be chosen |
Distance Between Profiles | 20mm | 20mm |
Recommended spacing between supports | 800mm | 800mm |
Average Weight | 7.6 kg/m2 | 8.5 kgs/m2 |
Surface area per unit volume | 120 | 158 |
Drift loss limit | 0.001% | 0.0005% |